Heaters Set up Direct – Indirect
Department: Tool Department
Topic: Site Operations
Process: Heaters Set up Direct – Indirect
Objective
The proper setup and safe operation of both direct-fired and indirect-fire heater units used in outdoor or large indoor workspaces, ensuring efficient and sage heating in cold environments.
Background
Direct-fired heaters – are efficient because they convert nearly 100% of fuel to heat.
Indirect-fire heaters – use a heat transfer fluid to prevent direct contact with combustion gases. These are not to be used in wood frame structures.
Things to Consider
Direct-fire heaters
Advantages – Highly efficient, more power in a smaller unit, portable and convenient.
Disadvantages -Requires ventilation, require fresh air, and creates moister air.
Indirect-fire heaters
Advantages – Creates cleaner Air, Creates drier air.
Disadvantages – Less portable and less convenient, less efficient, and less precise temperature control.
Direct-Fire Heater Set Up
-
Hose and Regulator Assembly (If not already assembled)
-
Apply pipe thread compound at threaded connections and connect the components together and tighten securely.
-
Tradesman 170 Propane Gas
-
Thread swivel nut end of hose-to-hose threads on adapter (Fig 1).
-
Apply compound at 3/8-inch threads of hose adapter (Fig 1).
-
Thread hose adapter to inlet of gas control valve (Fig 1)
-
Apply compound thread rigid hose end into regulator outlet (Fig2).
Tradesman 400 LP
-
Apply compound and thread rigid hose end into gas inlet at heater (Fig 3)
-
Apply compound at ¼-inch threads of hose adapter and thread into regulator outlets (Fig4).
-
Thread swivel nut end of hose-to-hose threads on adapter (Fig 4).
-
Tradesman 170 Natural Gas
-
Apple pip thread compound at threaded connections and connect the components together (Fig 5).
-
When using propane as the fuel.
-
Assemble the components shown in below (Fig 6).
-
Connect POL nut and stem (Fig 7).
-
When using Natural Gas as the fuel (Do NOT use the POL fitting).
-
Ensure the natural gas supply has line pressure of minimum 2 PSIG up to a maximum 20 PSIG
-
Connect the hose to the regulator’s outlet and at the heater’s gas inlet
-
Connect the regulator to the natural gas supply using the appropriate fittings.
-
Tighten all connections securely.
Connecting Propane Regulator to Propane Gas Supply
-
At the inlet of the regulator is a male nut and stem called a POL.
-
Remove cap from the POL
-
Insert POL stem into the valve on the propane fuel container.
-
Thread the nut counterclockwise into the container’s valve.
-
Tighten the nut securely with wrench.
-
Slowly open the tank or cylinder valve.
-
This will prevent lock-up of the excess flow valve within POL stem.
-
Check all connections for leaks
-
Do not use flame to check for leaks
Start-Up Instructions
-
Connect the heater’s electrical cord to an approved electrical outlet.
-
Open the gas supply valve slowly.
-
For LP heaters, this is located on the tank or cylinder.
-
Set the fuel selector valve to the correct position (Fig 8)
-
Set thermostat on heater to a setting above room temperature.
-
The heater will start, and the burner will ignite.
-
Position the variable rate valve to desired heat (Fig 9)
Shut Down Instructions
-
Close the gas supply valve.
-
Allow the heater to burn off any fuel gas remaining in the gas supply line.
-
Set the thermostat to its lowest setting.
-
Disconnect the heater from its gas and electrical supplies.
Indirect- Fire Heater Set Up
-
Installation:
-
When transporting, use both lifting eyes located on sides of heater.
-
Place the unit on a level and non-combustible surface.
-
Minimum clearances from combustibles:
-
Outlet, minimum 10 ft
-
Sides, minimum 3 ft
-
Top, minimum 3 ft
-
Fuel Supply:
-
Ensure that for the surrounding temperature, size, and capacity of the propane supply cylinder is adequate to provide the rate BTI/HR input to the heater.
-
Visually inspect the hose assembly
-
Ensure protection of hose from high traffic areas.
-
Purge air from line and wait 10 minutes from ga to dissipate
-
Check hose any gas leaks
-
Fuel hose must be UL approved
-
Electrical:
-
Electric cable extensions must be 150V minimum to ensure proper operation.
-
Exhaust Flue Pipe:
-
The unit is to be connected to a flue pipe with adequate draft
-
This ensures proper start and operation of the unit
-
The flue pipe is to be made of non-combustible materials and clearances from combustible materials must be a minimum 8 inches (temperature of flue gases is approximately 410°F).
-
Discharge Ducting (Warm Air):
-
Minimum clearance from combustible materials is 4 inches.
-
Use steel ducting or fabric ducting capable of withstanding maximum temperature of 225℉
-
Maximum length of duct: 50 ft (straight).
-
Duct Diameter: 12 inches.
-
Make sure that the duct is safely and properly fastened to the outlet.
-
Avoid sharp bends and corner to ensure maximum air flow.
-
Avoid back pressure/heat accumulation in heater.
-
To conserve heat duct piping can be wrapped with concrete blanket avoid getting to close to discharge.
Failure to comply with these recommendations could result in a shutdown of unit.
Start up
-
Check that the control switch on the control box is in the position “0” (STOP).
-
Pre-select desired temperature on the room thermostat.
-
The temperature must be set higher than the ambient temperature.
-
The temperature must be set higher than the ambient temperature.
-
Open all possible shut-off devices of the fuel supply lines.
-
Turn the control switch on the control box to position “1” (HEATING).
-
When the ambient temperature level is low, the burner switches on automatically.
-
The fan does not switch on until the set temperature as been reached (takes approximately 1-5 minutes).
-
After starting up:
-
The heater will operate automatically by the thermostat.
-
The thermostat and burner sensor control the running sequences of the burner and fan sensor controls the fan function.
-
Overheat limit reset controls (STB) and shuts off the heater (burner) in the case of overheating.
-
The unit can also be used for ventilation purposes only, if needed
-
Turn the control switch on the control box to position “2” (VENTILATION).
-
Unit is now in the continuous ventilating mode.
-
Heating is not possible in this mode.
Shut Down
-
Turn control switch to position “0” (STOP).
-
Close all fuel supply.
Important: The air supply fan continues to run to cool down the combustion chamber/heater exchanger. The fan can restart for several times before finally switching off.